C200Hα series analog module fault judgment 1 ERROR light is on, check N+9 channel, judge error according to error code;
2 ERROR light and RUN light are not lit, it is the special IO unit out of the allowable range and IO bus error.
CJ/CS series analog module fault judgment 1 judgment indicator;
led
significance
Indicator light
Operating state
RUN (green)
Operating
bright
Normal operation mode
not bright
The unit has stopped exchanging data with the CPU unit
ERC (red)
The unit has detected an error
bright
An alert has occurred (such as disconnected detection) or the initial settings are incorrect.
not bright
Normal operation
ADJ (yellow)
Adjusting
flash
Operate in offset/gain adjustment mode
not bright
Other cases
ERH (red)
CPU unit has an error
bright
There is an error in exchanging data with the CPU unit
not bright
Normal operation
a. The RUN and ERC lights are on, the ERH light is off, check the 00-07 and 14 bits of N+9;
b. The RUN lamp and the ERC lamp are on, the ERH lamp is off, the ADJ lamp is flashing, and the 12, 13, and 15 bits of the N+9 are checked;
c. The RUN light is off, the ERC light is on, and the ERH light is off. Check the 11 bits of N+9.
d. The RUN lamp and ERH lamp are on, the ERC lamp is off, the IO bus error is checked, the CPU unit monitors the error, and the CPU unit WDT error occurs.
e. The RUN lamp and ERC lamp are not lit, the ERH lamp is on, check if there is a duplicate unit number and special IO unit setting error.
2 The RUN light is on and the other lights are off, indicating that the module is normal. If there is no input or output, check the module settings.