Building insulation material combustion performance detecting device
SYL-14 type
Key words: building material flammability test device, GB8626 building insulation material combustion performance testing device, insulation material combustion performance test,
one,
Building insulation material combustion performance detecting device
Overview
The flammability tester for building materials is a product developed by our company according to GB8626 "Test method for flammability of building materials". This product can be tested for the flammability of building materials.
two,
Building insulation material combustion performance detecting device
The main parameters
1. The height of the box is 700×400×810mm
2, sample size 250 × 90mm
3, the maximum thickness of the test piece 60mm
4, burner nozzle aperture φ0.17mm
three,
Building insulation material combustion performance detecting device
Structure and installation
l, structure
The tester consists of a combustion test chamber, a burner, a test stand, a regulating valve and the like. Liquefied gas (propane) tanks are provided
2, installation
According to Figure 1, the base is placed in the box, and the fixing sleeve, sample holder, etc. are installed as shown. Place the burner in front of the specimen. The burner rod is screwed from the outer casing of the casing to the burner base. Connect the propane meter to the liquefied gas tank, connect the regulating valve to the other end of the propane meter with a plastic tube, and connect the regulating valve to the burner with a pneumatic tube.
four,
Building insulation material combustion performance detecting device
Test operation
1. Select the appropriate ignition positioner and place it on the top of the burner.
2. Place the sample in the sample holder and hang it.
3. After the burner is close to the sample, lock the ruler on the bottom plate.
4. Place the filter paper in the collection tray made of aluminum foil and place it under the test piece.
5. Raise the burner, open the pressure regulating valve knob, ignite the nozzle with an electronic igniter, gradually adjust the flame length to about 20mm, tilt the burner by 45 degrees, and ignite the sample according to the standard required distance.
Fives,
Building insulation material combustion performance detecting device
Precautions
1. Before the burner is ignited, the pneumatic regulating valve on the burner should be adjusted up, and then the pressure regulating valve knob is gradually adjusted. After ignition, the flame size can be adjusted by the pressure regulator knob, or it can be fine-tuned by the pneumatic adjustment valve.
2. Before ignition, the liquefied gas tank and the burner should be kept at a distance to ensure safety.
3. The smoke inside the box should be discharged outside through the exhaust hood.